Crane Power Line Clearance
OSHA Table A Distances
How far a crane has to stay from a power line, by voltage, and what OSHA requires before working anywhere near one.
Reviewed November 2026 against 29 CFR 1926.1408, 1926.1409, 1926.1411.
Table A: Minimum Clearance Distances
| Voltage (nominal kV, AC) | Minimum clearance |
|---|---|
| Up to 50 | 10 feet |
| Over 50 to 200 | 15 feet |
| Over 200 to 350 | 20 feet |
| Over 350 to 500 | 25 feet |
| Over 500 to 750 | 35 feet |
| Over 750 to 1,000 | 45 feet |
| Over 1,000 | Set by the utility owner/operator or a registered professional engineer qualified in power transmission and distribution |
Source: 29 CFR 1926.1408, Table A. "To" includes the upper value: over 50 to 200 means up to and including 200 kV.
The Three Options
First, mark the work zone and decide whether any part of the equipment, load line or load, at the crane's maximum working radius, could come within 20 feet of a power line. If it could, pick one:
- ✓Option 1: Deenergize and ground. Confirm from the utility owner/operator that the line is deenergized and visibly grounded at the worksite
- ✓Option 2: 20-foot clearance. Make sure nothing gets closer than 20 feet, using the encroachment precautions below
- ✓Option 3: Table A clearance. Get the line voltage and keep the Table A distance, using the same precautions. The utility must give the voltage within two working days of the request
Encroachment precautions for options 2 and 3: hold a planning meeting with the operator and crew, use non-conductive tag lines if tag lines are used, put up an elevated warning line, barricade or line of signs in the operator's view, and add at least one of these: a proximity alarm, a dedicated spotter in continuous contact with the operator, a range control warning device, a device that limits range of movement, or an insulating link.
Traveling Under or Near Power Lines With No Load (Table T)
| Voltage (nominal kV, AC) | Minimum clearance while traveling |
|---|---|
| Up to 0.75 | 4 feet |
| Over 0.75 to 50 | 6 feet |
| Over 50 to 345 | 10 feet |
| Over 345 to 750 | 16 feet |
| Over 750 to 1,000 | 20 feet |
Source: 29 CFR 1926.1411, Table T. The boom or mast must be lowered enough to meet these distances, and a dedicated spotter is required if any part of the equipment will come within 20 feet of the line.
5 Practice Questions: Power line clearance
From the question bank in the app. Pick an answer, then open the explanation. For a scored test, try the NCCCO core practice test.
Power Lines
1. What is the minimum clearance a crane must keep from a power line rated 50 kV or less?
- A10 feet
- B6 feet
- C15 feet
- D20 feet
Show answer
Answer: A. 10 feet. OSHA requires at least 10 ft for lines up to 50 kV — more as voltage rises.
Power Lines
2. Using Table A, what is the minimum clearance from a power line rated over 200 kV up to 350 kV?
- A20 feet
- B15 feet
- C25 feet
- D35 feet
Show answer
Answer: A. 20 feet. Table A requires 20 ft of clearance for lines over 200 kV up to and including 350 kV.
Power Lines
3. Working near a line rated over 750 kV, the minimum clearance is…
- A45 feet
- B20 feet
- C25 feet
- D35 feet
Show answer
Answer: A. 45 feet. Above 750 kV up to 1,000 kV, minimum clearance is 45 feet.
General Knowledge
4. According to OSHA 1926.1408, for power lines that are below 350 kV, but the exact voltage is unknown, what is the minimum clearance distance required?
- A20 ft
- B10 ft
- C15 ft
- D25 ft
Show answer
Answer: A. 20 ft. OSHA 1926.1408 requires a minimum 20-foot clearance when line voltage up to 350 kV is unknown.
Rigging
5. Under Subpart CC, how must power lines be treated by default?
- APresumed energized unless the utility confirms they are deenergized and visibly grounded at the worksite
- BPresumed safe if no crackling is heard
- CPresumed insulated unless marked otherwise
- DPresumed deenergized after the utility is notified
Show answer
Answer: A. Presumed energized unless the utility confirms they are deenergized and visibly grounded at the worksite. The employer must assume all power lines are energized unless the utility owner/operator confirms the line has been and continues to be deenergized and visibly grounded at the worksite.
Study the Whole Exam, Not 20 Questions
5,000+ practice questions across Core and every specialty, load chart trainers with the rating table on screen, timed exam simulations, and the pass guarantee.
Power line clearance: Questions & Answers
How far must a crane stay from a power line?
What is the 20-foot rule for cranes?
What if the line is over 350 kV?
Can I assume a power line is dead?
What does a dedicated spotter do?
This page is a study aid. It summarizes federal OSHA rules and industry standards and is not a substitute for the regulation, the manufacturer's manual or your employer's procedures. State plans and site rules can be stricter.